- Fail safe vs fail secure: electric strikes and maglocks
Fail safe vs fail secure: electric strikes and maglocks
Fail safe hardware unlocks when the power is cut, and fail secure hardware stays locked from outside.
After that choice come the voltage, the door and frame prep, and the power supply that runs it.
This answer was checked on against the sources listed on this page.
What decides the part number?
Fail safe or fail secure, the type of device, the voltage, the lock and frame it has to suit, and the power supply decide the part number.
Fail safe or fail secure: which does the door need?
The door needs fail safe hardware if it must release when power is removed, and fail secure if it must stay locked from outside. The choice follows how the door has to behave in an alarm or a power cut, and it changes the part number: the HES 1006 strike, for example, is fail secure as standard, with fail safe as a separate option.How does an electric strike work?
An electric strike replaces the strike in the frame and releases the latch. It has to suit the lock or exit device latch and the frame, and its voltage, 12 or 24 V DC, matches the power supply; the HES 1006 draws 480 mA at 12 VDC or 240 mA at 24 VDC, the figure to size the supply from.Is a maglock fail safe?
Yes, a maglock is fail safe: a magnetic lock holds the door with an electromagnet and has no latch, so it releases when power is cut and always needs a way to release for people leaving; the Securitron M62 holds 1,200 lb. Whether one is allowed on a door, and how it has to release, depends on the building. We supply listed hardware and confirm in writing the part number and options you have chosen. We are not code consultants; your Authority Having Jurisdiction (AHJ) makes the final call.What is a standalone keypad lock?
A standalone keypad or touchscreen lock stores its codes in the lock and runs on batteries, with no wiring and no network. We do not sell app, wifi or networked smart locks.What powers electrified hardware?
Strikes, magnetic locks and electromechanical locks need a power supply sized to the load, and an electrified hinge or power transfer to carry the wire into the door.Fail safe vs fail secure: what happens when the power goes off?
This section and those after it, unless dated otherwise, were checked on against the sources listed on this page.
Fail safe hardware needs power to stay locked, so it unlocks when the power goes off; fail secure hardware needs power to unlock, so it stays locked. HES calls the two power to lock and power to unlock. The mode governs the entry side: HES notes that, maglocks excepted, most electrified hardware allows free egress at all times in either mode.
What each mode does at the door
- Fail secure strike: with the power off the keeper stays locked, so the door stays locked from outside while people inside still leave through the lock or exit device.
- Fail safe strike: with the power off the door opens from outside. HES’s surface strike instructions describe fail safe keepers as unlocked without power and locked when power is applied.
- Maglock: HES says electromagnetic locks are only available fail safe. With the power off the M62 lets go completely; Securitron’s instant release circuit leaves no residual magnetism.
- Exit device with electric latch retraction: HES says these are only available fail secure.
| Part | Fail mode | How it is set |
|---|---|---|
| HES 1006 | Fail secure as standard, fail safe to order | When ordered: fail safe is its own part number, ending -F |
| HES 1500 | Either | On site: ships fail secure; two screws on the back of the strike change it |
| HES 1600 | Either | On site, the same way as the 1500 |
| HES 9600 | Either | On site: ships fail secure; two selector stop pins change it |
| Securitron M62 | Fail safe only | Holds only while it has power |
HES’s own guidance puts fail safe on doors that must allow free egress on fire alarm activation or power failure, giving stairwell doors that require re-entry as its example, and fail secure where entry security is the concern. Its 1500 and 1600 instructions add that the suitability of fail secure operation is up to the local AHJ and that emergency exit hardware may be required. We supply listed hardware and confirm in writing the part number and options you have chosen. We are not code consultants; your Authority Having Jurisdiction (AHJ) makes the final call.
Electric strike vs maglock: which should you use?
Choose an electric strike when the door has a working latch lock or exit device, and set it fail secure if the door must stay locked in a power cut. Choose a maglock when there is no latch to work with and the door may unlock in a power cut: HES makes electromagnetic locks fail safe only, and a maglock needs its own release for people leaving.
Maglock vs electric strike, side by side on the parts we list:
| Question | Electric strike (HES 1006, 1500, 1600, 9600) | Maglock (Securitron M62) |
|---|---|---|
| What holds the door | The door’s own latch, caught by the strike’s keeper in the frame | An electromagnet on the frame head, pulling on a strike plate bolted through the door |
| Power off | Fail secure: stays locked from outside. Fail safe: opens | Lets go completely; fail safe only |
| Leaving the room | Through the lock or exit device; HES says free egress at all times | Only once its power is cut, by a switch, a sensor or a release in the door hardware |
| Frame work | 1006, 1500 and 1600 cut into the jamb at the ANSI 4-7/8 in strike prep; the 9600 is surface mounted with no cutting | Surface mounted on the frame head with collapsing blind nuts |
| Rated strength | 2,500 lb static (1006, fail secure), 2,000 lb (9600 catalog; its installation instructions give 1,500 lb), 1,500 lb (1500 and 1600); ANSI/BHMA A156.31 Grade 1 | 1,200 lb holding force; ANSI/BHMA A156.23 Grade 2 |
| Power use | Fail secure draws current only while released; fail safe while locked | Draws current the whole time the door is locked |
| Fire-rated doors | UL 10C in fail secure only (1006, 1500, 1600); the 9600 is not fire rated | UL 10C, certified as an auxiliary lock |
The strength figures are not like for like: the HES strikes are certified to ANSI/BHMA A156.31 and the M62 to A156.23, a different standard. A strike also inherits the lock’s behavior: HES’s selector guide notes that the existing locking hardware decides both which strike fits and the overall function of the opening, and the lock function code says what the outside lever does. See all electric strikes and magnetic locks.
Where running wire to the door is the obstacle, a standalone keypad lock replaces the lockset instead: the Alarm Lock Trilogy DL2700 stores up to 100 user codes and runs on five AA batteries, with a key override cylinder (Alarm Lock spec sheet ALA129K).
Which electric strike fits a mortise lock?
An electric strike for a mortise lock is one built for the ANSI 4-7/8 in strike prep, with a faceplate matched to the lock’s latchbolt and, where the lock has one, its deadbolt. For a mortise lock with up to a 3/4 in latchbolt and no deadbolt, HES’s selector guide lists its 1006, 1500 and 1600; for one with a 1 in deadbolt, the 1006 and 1600.
| Mortise lock | HES strike | What the strike does |
|---|---|---|
| Latchbolt up to 3/4 in, no deadbolt | HES 1500 (1500C), HES 1600 (CLB) or HES 1006 (CLB) | Releases the latchbolt |
| 1 in deadbolt used as a night latch only | HES 1600 (CDB) or HES 1006 (CDB) | Releases the latchbolt; the deadbolt stays retracted during traffic hours |
| 1 in deadbolt that locks the door out | HES 1006 with the HM or HTD faceplate | Will not release while the deadbolt is extended |
| 1 in deadbolt kept extended and recaptured | HES 1006CAS | Releases latchbolt and deadbolt together and holds the keeper open to recapture both as the door closes |
- Recapture: HES marks its 1006CS, 1006CDB, 1600 CS and 1600 CDB as not intended for continuous recapture of a 1 in deadbolt and points to the 1006CAS (HES lock cross reference).
- Faceplate by lock series: HES’s KM faceplates (1KM on the 1500 and 1600) fit the Sargent 7800, 8200 and 9200, Corbin Russwin, BEST and Accentra 8800 (formerly Yale Commercial) mortise locks; its KD faceplates fit the Sargent 7700 and 8100, Accentra 8700 and Dorma 9500. The 1500C, 1600 CLB and 1006CLB include both. HES gives these lists as recommendations and refers you to the lock maker’s documents.
- Strike position: HES sets the strike’s centerline 3/8 in above a mortise lock’s centerline; on a cylindrical lock the two line up (HES lock cross reference).
- Frame depth: the strike body is 1-3/8 in deep on the 1500, 1-5/8 in on the 1600 and 1-11/16 in on the 1006 (HES catalogs). Of the three, HES’s comparison chart shows only the 1500 installing in a fire-listed 2 in frame with 1/2 in drywall.
- Door pressure: HES notes that a mortise lock may need a strike with a deeper cavity, deadbolt support or preload capability, depending on latch design and door pressure; preload is pressure on the door that stops a standard strike releasing.
Which electric strike fits a cylindrical lock or a rim exit device?
A cylindrical lock with up to a 3/4 in latchbolt takes the same cut-in HES strikes, the 1006, 1500 or 1600 with the J or 1J faceplate, fitted centerline to centerline with the lock. A rim exit device takes a surface mounted strike matched to its latch, such as the HES 9600 for a Pullman latchbolt up to 3/4 in throw (HES lock cross reference).
- Pullman latch up to 3/4 in: the HES 9600 fixes to the face of the frame with no cutting and is not fire rated; HES’s 9500 takes the same latch and is listed as 3-hour fire rated.
- Pullman latch up to 1/2 in: HES 9400.
- SquareBolt-style latch (Corbin Russwin SecureBolt, Accentra SquareBolt): HES 9700.
- Adams Rite Starwheel or interlocking latch: HES 9800.
HES lists these for rim devices from all manufacturers, but its compatibility list dates from each strike’s launch and does not cover a device redesigned since, so check an older or altered device against its maker’s documents.
What power supply does an electric strike or maglock need?
An electric strike or maglock needs a DC supply at its own voltage, 12 or 24 V, sized for the current of every device it runs. From the makers’ sheets: the HES 1500 and 1600 draw 240 mA at 12 V DC or 120 mA at 24 V DC, the HES 1006 480 or 240 mA, the HES 9600 500 or 250 mA and the Securitron M62 250 or 150 mA.
| Part | 12 V DC | 24 V DC | Supply notes from the maker |
|---|---|---|---|
| HES 1006 | 480 mA | 240 mA | Continuous duty; well-filtered DC with under 1 V of ripple |
| HES 1500 and 1600 | 240 mA | 120 mA | DC for continuous duty; on AC, intermittent duty only (10 percent duty cycle, 2 minutes on at most) |
| HES 9600 | 500 mA | 250 mA | Continuous duty on DC |
| Securitron M62 | 250 mA | 150 mA | Senses 12 or 24 V itself; full-wave rectified DC isolated from earth ground; AC or half-wave power will not do |
- Fail safe draws power the whole time it is locked. By HES’s definitions a fail safe device needs power to stay locked and a fail secure one only to unlock, so a fail safe strike or a maglock draws its current for as long as the door is locked. That is why a fail safe 1500 or 1600 runs on DC: HES rates them on AC for intermittent duty only. HES’s 2005M3 SMART Pac III cuts the initial voltage by 25 percent in timed or fail safe operation to extend a strike’s life.
- Add up every device. Securitron’s own worked example puts an M62 (0.25 A), a DK-26 access unit (0.16 A), an XMS motion sensor (0.05 A) and an EEB2 timer (0.025 A) on one 12 V DC supply: 0.485 A, rounded up to 0.6 A, which Securitron’s table wires in 18 gauge for a 200 ft run from the supply.
- Wire gauge rises with the run. HES gives minimum gauges by round-trip length: the 1006 takes 18 gauge up to 200 ft at either voltage, and the 1500 and 1600 take 20 gauge at 24 V for the same run.
- Meter the supply first. HES warns that many supplies run above their rating and that input more than 10 percent over the solenoid rating may cause severe damage, and it requires wiring to the National Electrical Code, NFPA 70.
What does the building code say about maglocks on exit doors?
The 2021 International Building Code (IBC) permits a maglock or other electric locking system on doors in the means of egress, in any occupancy except Group H, where it releases by door hardware (section 1010.2.11) or by a sensor (section 1010.2.12) and meets that section’s conditions. Both sections require the lock to unlock automatically when it loses power. They matter most for a maglock, the one product HES names as not allowing free egress at all times.
Section 1010.2.11: door hardware release
- The hardware on the door leaf has an obvious method of operation, readily operated under all lighting conditions, and works with one hand.
- Operating it directly interrupts power to the electric lock and unlocks the door immediately.
- Loss of power to the locking system unlocks the door.
- Where panic or fire exit hardware is required by section 1010.2.9, operating it also releases the electric lock.
- The locking system units are listed to UL 294.
Section 1010.2.12: sensor release
- A sensor on the egress side detects an occupant approaching and unlocks the door; loss of power to the sensor, the lock or the locking system unlocks it too.
- A manual unlocking device 40 to 48 inches above the floor and within 5 feet of the secured doors, with ready access and a sign reading “PUSH TO EXIT”, directly interrupts power to the lock, independent of other electronics, and keeps it unlocked for at least 30 seconds.
- Activation of the fire alarm system, the automatic sprinkler system or the fire detection system, where provided, unlocks the lock, and it stays unlocked until the fire alarm system has been reset.
- Emergency lighting on the egress side, and locking system units listed to UL 294.
Section numbers move between editions. The 2021 panic hardware section (1010.2.9) lets doors with panic or fire exit hardware in Group A or E be electrically locked under 1010.2.11 or 1010.2.12; in the 2024 edition the panic hardware section (1010.2.8) points to section 1010.2.10 instead, and in the 2018 edition (1010.1.10) to 1010.1.9.9 or 1010.1.9.10. Delayed egress (1010.2.13) and controlled egress in Groups I-1 and I-2 (1010.2.14) have their own sections in the 2021 edition. Read the edition your jurisdiction has adopted.
Securitron’s M62 instructions wire for release the same way: manual switching or automatic triggering from a fire alarm system, through a switch or relay that breaks the power. The M62 data sheet lists ANSI/UL 294, and HES lists UL 294 for the 1006, 1500, 1600 and 9600. We supply listed hardware and confirm in writing the part number and options you have chosen. We are not code consultants; your Authority Having Jurisdiction (AHJ) makes the final call.
Can an electric strike or maglock go on a fire-rated door?
HES lists its 1006, 1500 and 1600 strikes as UL 10C fire rated in fail secure mode only, at 3 hours on a single door and 1-1/2 hours on a pair, and the 9600 as not fire rated. UL certifies the Securitron M62 as an auxiliary lock for fire doors rated up to 3 hours with the B, D, BD or F suffix.
| Part | Fire rating the maker lists | Condition |
|---|---|---|
| HES 1006 | UL 10C: 3 hours on a single door up to 48 x 96 in, 1-1/2 hours on a pair up to 96 x 96 in | Fail secure only |
| HES 1500 and 1600 | UL 10C: 3 hours on a single door, 1-1/2 hours on a pair | Fail secure only |
| HES 9600 | None: HES lists it as non-fire rated | HES’s 9500 takes the same latch and is listed as 3-hour fire rated |
| Securitron M62 | UL 10C, in UL’s auxiliary locks category: up to 3 hours with the B, D, BD or F suffix, up to 1 hour with the G suffix | Fail safe by design |
HES’s surface strike instructions say that converting a 9400, 9500, 9600 or 9700 to fail safe negates the unit’s fire rating, and fail safe should not be used in fire rated or windstorm resistant applications. HES’s selector guide lists a fire-rated assembly (NFPA 80 fire doors) among the special requirements to settle before choosing a strike. We supply listed hardware and confirm in writing the part number and options you have chosen. We are not code consultants; your Authority Having Jurisdiction (AHJ) makes the final call.
What do we confirm before it ships?
Before anything ships we confirm in writing: fail safe or fail secure, voltage, the lock or exit device it works with, the frame or door prep, and how it will be powered.
Every figure in this guide comes from the documents listed below: manufacturers' catalogs, templates and installation instructions, standards bodies' summaries, and the published code text with its official guides. We supply listed hardware and confirm in writing the part number and options you have chosen. We are not code consultants; your Authority Having Jurisdiction (AHJ) makes the final call.
Sources
The numbers and code sections on this page come from these documents, opened on the check dates shown above.
- HES 1006 Series catalog page (AADSS1203080, updated 6/11/2025)
- Securitron M62 Magnalock data sheet (AADSS1204562, updated 6/9/2025)
- HES, Fail Safe versus Fail Secure (hesinnovations.com, read 1 October 2026)
- HES, Electric Strike Essentials (hesinnovations.com, read 1 October 2026)
- HES 1006 Series product page, fire ratings (fail secure only)
- HES 1006 installation instructions (AADSS1009170)
- UL certificate of compliance R9483, HES 1006 (AADSS1247371, issued 2023-10-17)
- HES 1500 Series catalog page (AADSS1203081, updated 4/2/26)
- HES 1600 Series catalog page (AADSS1203082, updated 4/2/26)
- HES 1500 and 1600 Series brochure with comparison chart (AADSS1090055, HES-087-0725)
- HES 1500 and 1600 installation and operating instructions (AADSS1053602)
- HES 9600 Series catalog page (AADSS1203093, updated 6/11/2025)
- HES 9400, 9500, 9600, 9700 and 9800 installation instructions (AADSS1053638)
- HES electric strike lock cross reference (AADSS1052973, updated 6/11/2025)
- HES electric strike selector guide (AADSS1058464, EMS-21-1225)
- HES electric strike overview brochure (AADSS1058482, HES-094-0226)
- HES fire-rated solutions page (9500 Series, 3-hour fire rated)
- Securitron M32, M62 and M82 installation and operating instructions (AADSS1058203)
- UL certificate of compliance R-R13976, Securitron M32 and M62 auxiliary locks (AADSS1216834, 2022-11-28)
- International Code Council, 2021 IBC egress code change monograph: proposals E48-21, E50-21, E51-21 and E53-21 reprint IBC 2021 sections 1010.2.9 and 1010.2.11 to 1010.2.14
- International Code Council, 2024 IBC egress code change monograph: proposal E58-24 reprints IBC 2024 section 1010.2.8
- International Code Council, BCAC proposal reprinting IBC 2018 sections 1010.1.9 and 1010.1.10
- Alarm Lock Trilogy T2 DL2700 spec sheet (ALA129K, 2025.11)
Series we list in this category
Related buying guides
Not sure which part you need?
You do not need a part number. Send a photo of the hardware and the door it sits on, plus the ship-to ZIP code, and we will identify it and quote it within one business day.